MAMP Series Explosion-proof Pressurized Control Cabinet

Certification

MAMP Series Explosion-proof Pressurized Control Cabinet

Home > Products > Explosion-proof Pressurized Control Cabinet > MAMP Series Explosion-proof Pressurized Control Cabinet

Used in chemical, oil refining, oil exploitation, offshore oil platforms, oil tankers, military and other hazardous areas;

Suitable for control of high-power electric heaters in hazard- ous areas and some equipment that requires on-site touch adjustment display;

Different installation methods are optional, such as hanging, floor-standing, piano table type.

Specific parameters and selection

Explosion protection

Gas explosion protection

Dust explosion protection

06: Ex db eb ib mb pzc IIC T4 Gc

07: Ex db eb pzc IIC T4 Gc/Ex pzc tb IIIC T135°C Dc

08: Ex db pxb IIC T6...T4 Gb/Ex db pzc IIC T6...T4 Gb

Ex pxb tb IIIC T80°C, T95°C, 135°C Db/Ex pzc tb IIIC T80°C, T95°C, 135°C Db

Conformity to standards

GB/T 3836.1, GB/T 3836.2, GB/T 3836.3, GB/T 3836.5, GB/T 3836.31, GB/T 3836.4

IEC 60079-0, IEC 60079-1, IEC 60079-2, IEC 60079-7, IEC 60079-31, IEC 60079-11

Electrical parameter

Rated voltage: Max.AC1500V 50/60Hz

Rated current: Max.1500A

Ambient Temperature Range and

Protection/Corrosion Protection Level

-60°C/-40°C/-20°C~+60°C, IP54/IP66, WF2

Material of exposed fastener

SS304/SS316 Stainless Steel

Enclosure material

Q235, Stainless Steel 304/316

Surface Finish and Color

Customized colors available, Stainless Steel default finish is brushed.

Air pressure

0.4~0.8 Mpa

Work pressure

200-600 Pa

Gas type

Inert gas, clean compressed air, nitrogen

Intake mode

Compensation type, ventilation type

Box structure type

Hanging type, floor type (left and right,up and down,integrated structure),piano table type

Product Working Principle

By installing all the electrical components of the user in a main cavityfilled with positive pressure clean medium, the air pressure in the maincavity is higher than the external air pressure, so as to effectively isolatethe ignition source and the explosive gas mixture, thereby achievingexplosion-proof purpose.

There are two intake types: positive pressure compensation type andpositive pressure ventilation type.

Compensation type: intermittent gas supply, positive pressure chambersealing is very good, gas consumption is also very small, generally used toconfigure non-explosion-proof touch screens that need to be touched;Ventilation type: continuous gas supply is required, which can take awaythe heat generated by the components installed in the positive pressurechamber at any time. The heat dissipation performance is good, and it issuitable for components with large heat generation inside, such as:high-power inverter, thyristor, high current circuit breaker, contactors, etc.;

According to the degree of transition of the dangerous area of the outer casing,it is generally divided into 2 categories.

1. Lower the explosion-proof hazardous Zone 1 to a non-hazardous zone for thepositive pressure housing;

2. Lower the explosion-proof hazardous Zone 2 to the non-hazardous zone for thepositive pressure housing;

Technical Requirements

Press the positive pressure start button. When the pressure in thepositive pressure chamber is greater than 60Pa, power suppliedautomatically to the positive pressure chamber. Positive pressurechamber enters the normal working stage. It should be re-purgedduring the purge. In the normal working stage, if the pressure is lessthan 60Pa, the user should provide0.2-0.8Mpa dry air.