Material: Nickel plated brass, stainless steel(304/316), Carbon steel Q235
Application: Unarmored cable mechanical clamping, suitable for use on Exd and Exe enclosure.
MCGd-A Unarmoured, Single seal
Thread Code
Metric thread
G/NPT Thread
Cable outer diameter(mm)
Ex-marks
Protection degree
02s16
M20*1.5
1/2
3.1~8.6
Ex db IIC Gb;
Ex eb IIC Gb;
Ex tb IIIC Db
IP66
WF2
02s
6.1~11.7
2
6.5~13.9
03s
M25*1.5
3/4
3
11.3~19.9
4
M32*1.5
1
17.0~26.2
5
M40*1.5
1 1/4
23.6~32.1
06s
M50*1.5
1 1/2
31.5~38.2
6
35.8~44.0
07S
M63*1.5
41.7~50.0
7
47.5~56.0
8
M75*1.5
2 1/2
55.0~62.0
08S
62.0~68.0
9
M90*2
67.0~79.0
MCGd-BI Unarmoured, Single seal
8~10
Ex db IIC Gb;Ex eb IIC Gb;Ex tb IIIC Db
IP66WF2
9~14
11~18
14~23
17~30
24~38
30~42
M90*1.5
38~55
M100*1.5
42~75
MCGd-BII Unarmoured, Single seal
/
Ex db IIC Gb
Ex de IIC Gb
Ex tb lllC Db
M20×1.5
6~12
M25×1.5
M32×1.5
17~25
M40×1.5
24~32
M50×1.5
31~39
M63×1.5
38~44
43~54
56~66
10
M110*1.5
72~81
MCGd-C Armored, Double seal
Material: Nickel plated brass , stainless steel (304/316)
Application:Armored cable mechanical clamping, suitable for Exd and Exe enclosure.
Outlet cable ΦA
Inlet cable ΦB
6.1~13.1
02S
9.5~15.9
12.5~20.9
19.9~26.2
23.7~33.9
27.9~40.4
35.2~46.7
40.4~53.0
45.6~59.4
54.6~65.8
M75×1.5
55~62
59~72
62~68
66.7~78.4
M90×2
67~79
76. 2~90.3
MCGd-E Armored, Single seal, with compound, Cable routing
Threadcode
Threadspecification
Stainless steel material
Brass nickel plated material
Protectiondegree
Passage Range
(Before Stripping)
(After Stripping)
Steel Wire
Diameter (mm)
NPT 1/2
≤11.7
6.1-13.1
0.8-1.25
9.5-15.9
02
≤12.6
12.5-20.9
03S
NPT 3/4
≤17.5
14-22
1.25-1.6
03
18.2-26.2
04
NPT 1
≤23.6
23.7-33.9
1.6-2.0
05
NPT 1 1/4
≤30
27.9-40.4
06S
NPT 1 1/2
≤36.6
35.2-46.7
2.0-2.5
06
≤41
40.4-53
NPT 2
≤47.9
45.6-59.4
07
≤53.7
54.6-65.8
NPT 2 1/2
≤59.9
59-72
08
≤64.2
66.7-78.4
2.5-3.0
09
M90×1.5
NPT 3
≤75.3
76.2-90.3
3.15-4.0
M100×1.5
NPT 4
≤85.6
86.1-101.4
MCGd-F Armored, with compound, steel pipe wiring
Application: Armored cable mechanical clamping, suitable for Exd and Exe enclosure.
Thread code
Stainless steel material(mm)
NPB material(mm)
Ex-mark
01
M16×1.5
3/8
≤10
7~14
≤5.5
7~16
≤11
≤8
≤16
10~18
≤12
14~20
≤19
13~23
18~25
≤25
18~30
≤21
24~33
≤33
22~38
31~40
≤44
29~46
≤34
41~50
≤55
36~57
50~64
≤68
46~75
≤52
65~76
≤93
62~103
≤72
89~103
MCGd-G Unarmoured, Double seal
07s
MCGe-H Armored, Single seal
Application: Armored cable mechanical clamping, suitable for use on
Ex eb IIC Gb; Ex tb IIIC Db
MCGe-I Unarmored, single seal
Material: Nickel plated brass , stainless steel (304/316),carbon steel (Q235)
Application: Unarmored cable mechanical clamping, suitable for.
MCGe-J Single seal, GRP material
Material: Engineering plastics(Unarmored, single seal)
Application: Unarmored cable mechanical clamping, suitable for Exe enclosure.
Threads
01S
4~8
G3/8
6~10
G1/2
8.5~14
G3/4
12.5~18
G1
G1 1/4
31~41
G1 1/2
35~45
G2
44~51